Welcome to SIDPH!

CORE COMPETENCIES

SIDPH dew point instruments has been designed to make continues measurement of the dew point in air and gases.Timely detection and handling of compressed air drying process problems.
It can extend the life of compressed air system components; to avoid some problems occur during compressed air system operation and maintaining efficient system operation, thus ensuring product quality and stability. Not only for applications related to air or gas drying. But also in many other industrial processes, ,as we all known that well-monitored dew points are crucial to the overall process .

PRODCUT

FM650 online dew point meter

SPECIFICATIONS£º

Designed for industrial spot checking and field calibration

Corrossive resistance

Excellent stability save your calibration costs

Dew point measuring range -60~+60¡ætd

Display humidity,temperature and dew point with curve interface

4-20mA/0-10V and RS485 

Alarm indicator and relay control



FM650 designed with the latest advanced digital technology, it is a new generation classic product for temperature ,humidity and dew point measurement .

digital signal processing and transmission ensure the product is high precision and reliable, transmission cable signal attenuation and interference will

not affect the accuracy. Calibration data is stored in sensor, so the instrument no need to re-calibration if you want replace the transmitter. our transmitter

suitable for different applications such as power plants, metallurgy,scientific research, health and quarantine, food storage, medical equipment, environmental

experiments,  calibration, paper and textile and other industrials,especially for the acid and alkali gas measurement, hydrogen, SF6, , Carbon monoxide, oxygen.


TECHNICAL DATA
Measurement range


Dew point£º-60~+60¡ætd
Temperature£º-50~100¡æ
Humidity£º0~100%RH
Accuracy Dew point£º¡À2¡æTd
Temperature£º¡À0.2¡æ
Humidity£º¡À0.8%RH
Pressure 20bar
Detect gas non-strong corrosive gases
Temperature -50~100¡æ
Gas flow rate > 2 L/min
Response time T63<12s
Output signal 4-20mA/RS485
Relay control Optional two way relay
Mechanical Connection G 1/2¡± thread  (ISO 228/1)
Supply voltage DC24V (consumption ¡¶10W)
Protection class IP65 Compliance with UL94-HB
Housing material 316stainless steel
Repeatability <0.5%RH ;<0.1¡æ
Drift/Year <1%RH;<0.1¡æ
EMC Compliance with 04/108/EG
CE Certified

DIMENSIONS
CONSULTING SIDPH SALES ENGINEER